Understanding Hidden Gum Challenges in SFFF Foams
As the fire protection industry continues its transition away from PFAS-containing firefighting foams, Synthetic Fluorine Free Foams (SFFF) are becoming increasingly important for Class B fire protection. But while much of the discussion around SFFF focuses on fire performance and environmental considerations, another factor deserves attention: the stability of the polymers used in some foam formulations.
One issue highlighted by Fomtec is what it describes as “hidden gum” – the use of partially hydrated natural polymers that can influence the viscosity and long-term stability of a foam concentrate.
Understanding how these polymers behave is important for fire departments, airports, oil and gas facilities, petrochemical sites, marine applications and other high-hazard environments where firefighting foam systems must operate reliably when needed.
What Is “Hidden Gum” in SFFF Foams?
Natural polymers have been used in firefighting foam formulations for decades. They can help strengthen the foam blanket, slow drainage, improve heat resistance and provide greater resistance to burnback.
Common examples include natural polymers such as xanthan gum and guar gum.
The challenge is that adding polymers to a foam concentrate can also increase its viscosity. Higher viscosity can affect pumping, proportioning and the ability of the concentrate to move efficiently through a fixed foam system.
According to Fomtec, some SFFF formulations use partially hydrated polymers to maintain a relatively manageable viscosity inside the container while still obtaining the performance benefits of polymers when the foam is produced.
This approach can create what Fomtec calls “hidden gum” – a polymer that has not reached its full hydration state and may therefore have the potential to change its behaviour later.
Why Does Foam Viscosity Matter?
Viscosity is more than a laboratory measurement. It can directly affect how a firefighting foam concentrate behaves within a suppression system.
If viscosity changes significantly during storage or operation, it may influence:
- Pump performance
- Pressure loss through pipework
- Foam proportioning accuracy
- Filters and strainers
- Nozzle performance
- Discharge characteristics
- Overall system reliability
This is particularly important because foam systems are designed around specific flow characteristics. A concentrate that behaves differently from when it was originally installed can potentially create challenges for equipment that was selected according to its original properties.
How Can Water Affect Partially Hydrated Polymers?
One of the key concerns surrounding partially hydrated polymers is their response to water.
Foam concentrate storage systems can be exposed to moisture and, depending on the installation, small amounts of water may potentially enter a tank or system. When partially hydrated polymers come into contact with additional water, they can continue to hydrate, swell and increase viscosity.
Fomtec’s published testing examined how foam concentrate viscosity changed following water addition. Its reported testing found that several competitive AR-SFFF products experienced significant increases in normalised viscosity when water was added.
The potential concern is not simply that a product becomes thicker. A substantial change in viscosity can affect how the concentrate moves through the complete foam delivery system.
For example, increased viscosity could contribute to higher pumping demands, greater pressure losses or difficulties passing through filters and strainers. Changes in the concentrate’s physical characteristics could also affect proportioning and discharge performance.
The Importance of Long-Term Foam Stability
Firefighting foam concentrates are expected to remain usable for years, often while stored in demanding environments.
Temperature fluctuations, humidity, storage conditions and equipment compatibility can all influence the condition of a foam concentrate over its service life.
This means that evaluating a foam should involve more than looking at its initial fire test results.
Fire protection professionals should also consider questions such as:
- How stable is the concentrate during long-term storage?
- How does its viscosity change over time?
- How does it respond to water contamination?
- Is the concentrate compatible with existing proportioning equipment?
- What inspection and testing programme is recommended?
- Has the foam been evaluated with the intended discharge equipment?
These considerations are particularly relevant when converting an existing system from a PFAS-containing foam to an SFFF alternative.
SFFF Performance Depends on More Than the Concentrate
The transition to fluorine-free firefighting foam is not simply a matter of replacing one liquid with another.
SFFF formulations can have different physical and performance characteristics, and the finished foam produced by a particular discharge device can have a major influence on fire suppression performance.
Fire Product Search has previously examined the challenges associated with SFFF performance, including differences between formulations, fuels, discharge devices and testing requirements. The industry is increasingly recognising that foam concentrate, proportioning equipment and discharge equipment need to be considered together rather than treated as completely independent components.
What Should Fire Protection Professionals Look For?
When selecting an SFFF concentrate, fire protection professionals should look beyond headline fire performance claims.
The physical properties of the concentrate, its compatibility with existing equipment and its expected behaviour during storage are all important considerations.
Manufacturers should be able to provide technical information covering viscosity, storage conditions, compatibility and relevant testing. Where a foam relies on polymers, understanding the polymer technology and its hydration state can also provide useful information when assessing long-term reliability.
Regular inspection and testing are equally important. Foam concentrates should be maintained according to the manufacturer’s recommendations and relevant fire protection standards.
For existing installations, a transition programme should also consider cleaning requirements, compatibility with existing tanks and pipework, proportioning equipment and the characteristics of the new foam.
Looking Beyond the Initial Fire Test
The move toward SFFF represents an important development in firefighting foam technology. However, achieving reliable protection requires more than demonstrating that a foam can extinguish a fire under controlled test conditions.
Long-term behaviour matters.
A foam concentrate must remain suitable for pumping, proportioning and discharge throughout its service life. If its physical characteristics change significantly after installation, the performance of the complete system may be affected.
The issue of “hidden gum” highlights why polymer stability deserves greater attention as the industry continues its transition to fluorine-free solutions.
Partially hydrated polymers may provide useful formulation benefits, but their response to water, storage conditions and time should be understood before they are relied upon in high-consequence fire protection applications.
For end users, system designers and fire safety professionals, the priority should be clear: select firefighting foam based not only on fire test performance, but also on long-term stability, equipment compatibility and predictable system operation.
As SFFF technology continues to develop, greater transparency around formulation, polymer behaviour and long-term performance can help the industry make better-informed decisions and ensure that firefighting foam systems remain ready when they are needed most.
For more information please visit Fomtec website.