Industrial fuel-storage facilities face increasingly complex fire risks, requiring suppression systems that can respond instantly, operate reliably, and scale across large sites. As part of a major safety upgrade, a leading storage tank operator in Hungary commissioned a full assessment on how to expand its existing PI Foam System to protect additional tanks, bunds, and loading areas. The resulting engineering study demonstrates how easily this advanced system can scale from a single tank to full-site protection.

A Growing Need for Scalable Fire Protection

A major storage tank company in Hungary, operating on Csepel Island along the Danube River, is planning to extend its current fixed fire-fighting foam system. The facility, operated by Oiltanking Hungary, already relies on the first-generation PI Foam System to protect one gasoline storage tank. After years of dependable service, the company requested a design for a site-wide expansion to safeguard three additional diesel tanks, their bund areas, pump stations, and loading areas for trains, trucks, and barges.

This upgrade would ensure the system can respond to simultaneous fire events—an essential feature for fuel terminals where fire can spread rapidly across tank farms.

Why the PI Foam System Stands Out

The PI Foam System differs from traditional pump-dependent foam systems. Its core component is a pressurised foam storage vessel capable of releasing extinguishing foam instantly and at high volume.

Key Features of the System

  • Pump-free operation: Foam is generated within the vessel itself, reducing maintenance and eliminating pump-related failure points.
  • Temperature-resistant piping: Foam is sent through a network of durable pipes leading to each protection zone.
  • Fast activation: Sensors signal valves to open, unleashing a rapid wave of foam within seconds.
  • Scalable performance: Not limited by pump output—ideal for facilities of any size.
  • Reusable foam: Any foam left in the vessel or pipelines after extinguishment is fully reusable.

These features provide an extremely reliable and cost-efficient alternative to manually staffed fire brigades or conventional deluge systems.

Designing a Facility-Wide Expansion

Swiss Fire Protection R&D (SFPRD), based in Sarnen, Switzerland, prepared a detailed engineering study to map out the expansion.

1. Zoning the Facility for Efficient Protection

Engineers divided the terminal into four extinguishment zones, with the largest zone covering all four storage tanks (5,270 m²). Each zone is connected to two independent pressurised foam vessels, each holding 38 m³ of foam solution.

The vessels are installed in a controlled-temperature enclosure to prevent freezing or overheating—critical for system reliability.

2. Handling Worst-Case Fire Scenarios

Oiltanking Hungary required the system to be capable of handling simultaneous fires affecting:

  • The largest gasoline tank (1,489 m² surface area)
  • Its associated bund area (389 m²)

Combined, this represents a worst-case fire area of 1,878 m², equivalent to a tank 43.5 m in diameter. The PI Foam System is engineered to deliver uninterrupted foam flow at the required density to suppress a fire of this magnitude.

3. Intelligent Foam Delivery

Only valves within the affected zone open during an incident, ensuring precise foam discharge without wasting resources or flooding unaffected areas.

Dispensers mounted around each tank and bund introduce foam directly onto the fuel surface, smothering flames quickly and preventing re-ignition.

Environmental Safety and Clean Recovery

After extinguishment, foam and fuel runoff are collected in a dedicated containment pit connected to a drainage system isolated from the sewage network. This prevents soil and water contamination, supporting the site’s environmental protection goals.

Optional Devices and System Versatility

The PI Foam System allows operators to attach:

  • Fire monitors
  • Hose stations
  • Portable foam delivery equipment

This flexibility enables both large-scale suppression and small-fire intervention, all using the same pressurised system.

Because it has minimal mechanical components, the system offers extremely low failure rates and significantly reduced operational costs.

A Technology with Expanding Applications

SFPRD continues to advance the PI Foam System, with new designs underway for:

  • High-rise buildings
  • Freight vessels
  • Industrial complexes

Its scalability makes it suitable for virtually any facility requiring rapid, reliable, and simultaneous fire extinguishment.

Final approval for the expansion project at Oiltanking Hungary is expected soon, marking a major step toward comprehensive site-wide fire protection.