XL-800™

Supplied by Niedner.

Niedner's most popular attack hose. Lighter and more compact than competitive attack hoses, XL-800™ is a 100% polyester double jacket hose lined with TPU elastomer with a service test pressure of 400 PSIG (2800 kPa). This is the Number One choice for high-rise backpacks. For everyday attack fire fighting, XL-800™ is easily handled and packs tightly. The waterway is oversized to maximize flow and minimize friction loss. A third less bulk than rubber covered hose, XL-800™ is flexible to -60ºF (-51ºC). The ENCAP™ treated outer jacket improves durability, reduces water absorption up to 40% enhances chemical resistance and adds color options. Meets or exceeds NFPA 1961and ZZ-H-451.

UL label available on 1 1/2", 1 3/4" and 2 1/2" (38, 45 and 64 mm) sizes. Factory tested to 600 PSIG (4200 kPa).

Stanadard Lengths: 50' and 100' (15,2 and 30.5 m)
 
Colors available: clear (white), green, red, orange, blue, purple, tan and yellow.


XL-800™ specifications

    * The hose shall be of double jacket construction with 100% virgin spun polyester yarn in both jackets.
    * There shall be a minimum of 10.0 filler yarns per inch in both the inner and outer jackets.
    * The thickness of the lining shall be 0.015" (391 µm) minimum and it shall be constructed of extruded T.P.U. elastomer.
    * The outside jacket shall be treated with ENCAP™ elastomer, which shall completely encapsulate the jacket fibers and not merely surface coat the jacket.
    * The hose service temperature range shall be -60°F to 150°F (-51°C to 66°C).
    * FM abrasion test of 15,000 cycles minimum and Taber abrasion test of 5,000 cycles minimum.
    * At 800 PSIG (5600 kPa), its elongation shall not exceed 10% of the initial hose length; it shall not warp more than 20 inches (51 cm) and should not rise from the test table.
    * The hose shall not twist more than 2 turns per 50 ft (15,2 m) while at 800 PSIG (5600 kPa).
    * Minimum service test pressure of 400 PSIG (2800 kPa).
    * Minimum proof test pressure of 800 PSIG (5600 kPa).
    * Minimum straight burst test pressure of 1200 PSIG (8400 kPa).
    * The hose while curved to a radius of 27" (69 cm) shall not burst at less than 1200 PSIG (8400 kPa).
    * Meets or exceeds NFPA 1961 and UL-19 specifications.